With Softing’s FG-200, it is possible to integrate up to four FOUNDATION™ Fieldbus (FF) H1 links into control systems supporting Modbus TCP or into FF asset management applications. The FG-200 provides redundancy and is suitable for use in hazardous areas. This device features fast access to process data, while making use of FF advantages like reduced cabling, central field device parameterization, comprehensive diagnostics, or intrinsically safe device segments.
The FG-200 is the successor product of FG-110.
FG-200 | ||
Hardware | Processor | Altera Cyclone V SoC with dual-core ARM Cortex-A9 |
Status LEDs (Gateway) | PWR (power supply), RUN (operation), ERR (error), RDL (redundancy link) | |
Status LEDs (Fieldbus) | FF H1 activity per link | |
Interfaces and Connectors | Ethernet | 2 * IEEE 802.3 100BASE-TX / 10BASE-T (only ETH1 supported) Connectors: RJ45 |
Fundation Fieldbus H1 | 4 FF H1 links, compliant to type 114 of FF physical layer profile (each link capable to operate independently as Link Master and/or Time Master) Transfer rate: 31.25 Kbit/s Fieldbus voltage range: 9 VDC ... 32 VDC, preferred voltage: 24 VDC Current consumption: 10 mA / link Connectors: 3-position screw connection, galvanically isolated | |
Physical Properties | Dimensions (H x W x D) | 100 mm x 35 mm x 105 mm |
Weight | Approx. 250 g | |
Power Supply | 18 VDC ... 32 VDC; SELV/PELV power supply mandatory; Typical input current: 200 mA, maximum input current: 1 A (allowing for in-rush current at switch-on) No power supply to FF H1 links through FG-200 HSE/FF Modbus | |
Operating / Storage Temperature | -40 °C .. +70 °C / -40 °C .. +85 °C (see detailed mounting description in user manual) | |
Relative Humidity | 10 % ... 95 %, non-condensing | |
Cooling | Convection, no fan | |
Coating | Conformal coating based on ANSI / ISA-S71.04 G3 | |
Mounting | DIN rail 35 mm | |
Protection Class | IP20 | |
Software | Protocols | FOUNDATION Fieldbus H1, FOUNDATION Fieldbus HSE, Modbus TCP |
Redundancy | Device redundancy compliant to type D-3 according to specification FF-593 | |
Conformity / Certifications | CE | EN61000-6-2, EN61000-6-4, EN55022 Limit Class A, EN55011 |
Electromagnetic Compatibility (EMC) | FCC CRF47, Part 15 Section 15.107 and 15.109 (Class A), VCCI Class A Information Technology Equipment 2002 | |
Vibration / Shock | DIN EN 60068-2-6 Vibration / DIN EN 60068-2-27 Schock | |
Hazardous Location Certifications | cULus: Class 1, Division 2, Groups A, B, C, D IECEx: Ex ec [ic] IIC T4 Gc ATEX: Ex II 3G ec [ic] IIC T4 Gc |
Scope of Delivery | |
Hardware | FG-200 |
Software | Download from the Softing website: Firmware, FF Configuration Tool, FF-DTM |
Documentation | Quick Startup Guide, User Manual |
Order Numbers | |
GLA-EK-024102 | FG-200 |
ACA-ZZ-020631 | Redundancy Link (3-pole), Cable (30 cm) for connecting redundant pairs of FG-200 |
Additional products and services | |
Installation solutions | When using the high-power trunk topology or FISCO, we offer in cooperation with R.Stahl, fieldbus infrastructure components with PROFIBUS PA and FOUNDATION fieldbus H1 – this ranges from power supply, physical layer diagnostics and field device couplers to termination resistors. |