FAQ – Frequently Asked Questions and Application Notes

We have documented the answers to the most frequently asked questions to enable you to easily and quickly find answers directly.

Gateways general

Use Search and Configure if the IP address of a Softing gateway is unknown or does not match the actual network environment. Search and Configure is usually part of the installation package. You can also install it directly from here:

SearchAndConfigure V1.46

This program can be used for searching and configuring connected Softing devices in the local network. It sends UDP packets from the local port 2360 to the remote port 2355.

Start the program by double-clicking “sac.exe” or click the corresponding item in the start menu. If you have more than one network adapters in your PC then please select first the correct network adapter in the drop-down menu. When clicking the Search buttonthe network will be scanned for connected Softing devices. The retrieved devices will be listed with their MAC address, device type, serial number, name, IP address, subnet mask and gateway.

 

Note:If no connected device is found please check the firewall settings.

By selecting the device and clicking the Configure button you can modify network parameters of the device without using its website. Changing the IP configuration requires the password fitting the selected device.

Please note that the IP settings cannot be changed for the Softing gateway epGatePN!

Warning:
Be aware that the device may reboot after successful reconfiguration.
The device may cause network problems if configured with incorrect settings

Start a web browser that supports JavaScript (Google, Chrome) to access the gateway from your PC.
When your web browser doesn’t support JavaScript or JavaScript is disabled, then you will not be able to access the gateway. In this case you will only see in the browser window the message “loading”.

PROFINET gateways (pnGate PA, pnGate PB, pnGate DP)

Make sure the PROFINET IP address that is configured in the PROFINET engineering tool (e.g. TIA portal) differs from the IP addresses that are used by Search and Configure, by the webserver and by the FDT application.

Using the same PROFINET IP address in TIA portal and in the webserver will cause an IP address conflict!

If you have not changed the password, then you can log in with the default password of the device.

Please note that the default password has changed up to the Firmware Version 1.10.

Old firmware version (< 1.10):
User Name: administrator
Password: fgadmin

new firmware Version (>= 1.10):
User Name: administrator
Password: FGadmin!1

Firmware update via the web interface of the gateway is only available from the firmware version 1.10 and higher.

If your gateway has an older firmware version, less than 1.10, then a firmware update cannot be made in this way. The gateway should be sent back to Softing. In this case please fill out the 'Product Repair Form' which can be found on the Softing web site and send it per mail to [email protected]

No log display on the pnGatePA / mbGatePB web page in the tab PROFIBUS or PROFIBUS IO -> Views -> Log.

Please make sure that no script blocker like e.g. "AdBlock Plus" or "uBlock Origin" is active on the website of the gateway.
If a script blocker is installed on your PC, please disable it and reload the webserver of the gateway. After that the corresponding logs can be displayed.

Warning:
If the pnGatePA is not parameterized via an engineering tool, the log display remains also empty in the PROFIBUS tab.

In the PROFINET Engineering Tool (Step 7 project, TIA Portal), the process data is "0" (zero) in the S7-3xx controllers.
The S7 controller does not report any error and SF LED (System Fault) is off.
The pnGatePA / mbGatePB report no errors and all status LEDs are green.
On the website of the gateway in the menu item PROFIBUS -> Views -> Log you can see on the corresponding slave that the "State" is Data Exchange.

Workaround:
In the HW Configuration window of the Step7 project, select the controller and right-click in the context menu and then select "Object Properties ...".

In the new window, switch to the "Cycle / Clock Memory" tab.

The default settings for an S7-300 are 128 for the two marked setting options.

Make sure that the "Size of the process image input area" or "Size of the process image output area" is 1 (one) greater than the max. offset of the modules in the HW Config. We recommend setting the value to the max size of the process image of the S7-3xx. (See data sheet S7 -> process image)

As the gateway does not supply power to the devices on a fieldbus segment, each segment of your PROFIBUS network requires its own power supply with power conditioning.

Softing recommends using the R. STAHL bus-Carrier Series 9419 and Fieldbus Power Supply Series 9412 products.

A maximum of 64 devices can be connected in total to a 4-channel pnGate PA Gateway.
There is no limit to a channel / PA segment. Any splitting of the devices in the PA segments is allowed, provided that the used power conditioner supplies sufficient power.

The Device Catalog entries are imported via "Import GSD" and stored in the gateway.

The PROFIBUS configuration of the segments is not saved in the gateway due to insufficient persistent memory. The configuration project only exists in the web interface. It is displayed in the Segment Configuration view on the right-hand side of the PROFIBUS Configuration window. The segment configuration can be saved in a file on the PC by selecting "Save Configuration".
The name of the segment configuration file is PROFIBUS-Cfg.json and is located in the personal download folder.

When restarting the gateway, the segment configuration is not being displayed. To make it visible, reload the previously saved configuration into the web interface via "Load Configuration".

The PROFIBUS Slave configuration is typically done in the PROFINET engineering system (e.g. Siemens TIA Portal) based on the generated GSDML file in the integrated web server of the gateway (Generic GSDML option).

What happens if there is a power outage?
The PROFIBUS configuration is not lost! The configuration data is available in the individual PROFINET controllers and it is provided by the PLCs upon connection establishment.

One of the functions of the integrated web server of a PROFINET gateway is to convert all necessary PROFIBUS GSD files into a single PROFINET GSDML file.
The PROFIBUS Slave configuration is typically done in the PROFINET engineering system (e.g. Siemens TIA Portal) where the generated GSDML file has to be imported.

First the needed GSD files should be imported into the web server. To do this log on to the user interface, select PROFIBUS -> Configuration, determine the engineering system, click “Import GSDs” in the side menu and select the GSD files you want to import. After the import was made, the selected files are visible in the Device Catalog.

Now there are two configuration possibilities. You can generate a dynamic or a static GSDML file with the integrated web server (PROFIBUS -> Configuration -> Generic GSDML / GSDML):

  1. By selecting “Generic GSDML” you will generate a dynamic GSDML file from the imported GSD files in the Device Catalog. Remember that the PROFIBUS configuration of the segments is not stored in the GSDML which implies that the assignment of the devices to the PROFIBUS channels and the parameters of the devices must be done in the PROFINET engineering system (e.g. TIA Portal). If you choose this option then you have to configure the used PROFIBUS Slaves in the engineering system.
  2. Clicking the “GSDML” in the side menu it will convert the GSD files used in the Segment Configuration to a static GSDML file. In this case the PROFIBUS devices and the used IO modules cannot be manually altered later in the PROFINET engineering system (e.g. TIA Portal).

Where is the generated GSDML file?
The generated GSDML file is located in the personal download folder. The GSDML file needs to be moved from the download folder into the TIA Portal project folder! The path is shown in the headline of the TIA Portal project.

How is the GSDML file installed in TIA Portal?
If TIA Portal is open and the GSDML file is located in the TIA Portal project folder then the GSDML file will be automatically installed.

Modbus gateways (mbGate PA, mbGate PB, mbGate DP)

The Device Catalog entries are imported via "Import GSD" and stored in the gateway.

The configuration project only exists in the web interface. It is displayed in the Segment Configuration view on the right-hand side of the PROFIBUS Configuration window. The project can be saved in a file on the PC by selecting "Save Configuration". The name of the configuration project file is PROFIBUS-Cfg.json and is located in the personal download folder.

When restarting the gateway, the Segment Configuration is not being displayed. To make it visible, reload the previously saved configuration into the web interface via "Load Configuration".

The configuration of the PROFIBUS slaves is not saved automatically. In addition to “Save Configuration”, the Modbus and Ethernet/IP gateways have an “Apply Configuration” function. “Apply Configuration” stores the configuration of the PROFIBUS slaves in the Modbus gateway as a binary file. The gateway always uses this binary file internally.
 
What happens if there is a power outage?
If the configuration was not saved on the gateway previously via "Apply Configuration", it will be lost during a power outage. Otherwise the configuration exists in the form of a binary file on the gateway itself.

Ethernet/IP gateways (epGate PN, epGate DP, epGate PA)

IP-Address of epGate PN can be changed on Ethernet IP side by means of the Molex-Tool. This tool is freeware. It doesn’t have to be installed on the PC. It can’t be started from a USB stick. Below is the link:

www.molex.com/mx_upload/superfamily/iccc/EtherNet_IPTool.html

mobiLink

This document describes how to activate the mobiLink licences.

This document describes how to enable the mobiLink DTM traces.

x

Softing Industrial

Headquarter

+49 89 456 56-340


Callback Service

USA, Canada and Mexico

+1 865 251-5252


Callback Service


«