PROFIBUS PA Tester (BC-230-PB)

Quick and Easy Bus Test

The Diagnostic Monitor is a versatile tool for testing PROFIBUS PA during operation. It is powered by the fieldbus so that no battery or external power source is required.
The monitor is also suitable for use in hazardous areas.

  • No Battery or External Power Source Required
  • No PC or Notebook Needed for Testing the Bus
  • Clear OK/BAD Classification of Test Results

Universal Application

The PROFIBUS PA Diagnostic Monitor allows testing of the bus physics. In addition, it verifies that the communication between the bus devices is stable. This makes it a universal tool for setup and commissioning, documentation, acceptance testing, preventive maintenance, and troubleshooting.

Very Simple to Use

A display and two function buttons provide outstanding ease of use. The bus test starts automatically when the tool is connected to a PROFIBUS PA network. The test results are clearly classified as either OK or BAD. This tool is an ideal choice even for less experienced users.

Fully Automatic Bus Test

After attaching the tool to the PROFIBUS PA network, the Diagnostic Monitor is powered by the fieldbus and automatically starts testing the segment without operator intervention. If the measured data exceeds the tolerance limits, the operator is informed in plain text.
At the segment level, the tool determines the segment voltage as well as average noise and peak noise for three frequency ranges. Short circuits between the individual signal wires and the cable shield are reliably detected.
At the field device level, the Diagnostic Monitor reports all frame retransmissions and all devices added or dropped during bus operation. The current and the lowest signal levels of all devices are also determined.
No PC or notebook is needed for testing the bus. If required, the PROFIBUS PA Diagnostic Monitor stores the test data for later transfer to a PC via USB. The detailed test reports can be imported to Microsoft® Excel or exported as text files.

Input voltage:Fieldbus mode: 8 to 32 VDC, USB mode: 4.1 to 5.5 VDC
Max. input current:Fieldbus mode: 10 mA *, USB mode: 30 mA
Power dissipation:Fieldbus mode: max. 320 mW (at 32 VDC), USB mode: max. 165 mW (at 5.5 VDC)
Operating temperature:–20 to +50 °C **
Dimensions:146 x 88 x 28 mm
Weight:378 g
Case material: ABS
DC voltage measurement range:8 to 32 VDC ± 0.5 VDC
Signal level measurement range:0.12 to 2 Vpp ±10% ±0.025 Vpp
LF noise measurement range:50 Hz to 4 kHz, 0 to 1000 mVpp ±15% ±25 mVpp ***
FF noise measurement range:9 kHz to 40 kHz, 0 to 1000 mVpp ±10% ±25 mVpp ***
HF noise measurement range:90 kHz to 350 kHz, 0 to 250 mVpp ±20% ±25 mVpp ***
ConformityCE, FCC
Hazardous area approvals FM USA and Canada:
—Class I Division 2 Groups A, B, C and D T4
—Class I Zone 2 Group IIC T4
—Class I Division 1 Groups A, B, C and D T4
—Class I Zone 0 and 1 Ex/AEx ia IIC T4
ATEX Ex ia IIC T4
ATEX Ex nL IIC T4
ATEX Ex ic IIC T4
Data transfer to PCVia supplied PC software for Windows 2000, XP and VISTA, Windows 7 (32/64 bit) and USB interface version 1.1 or 2.0
*  In  fieldbus  mode  the BC-230-PB  is powered by the  fieldbus and draws approximately 9.4 mA of current from the segment (depending on bus voltage and ambient temperature).
**  Display update speed is impaired below –10°C.
*** Vpp = Volts peak-to-peak; excessive noise adjacent to the fieldbus frequency (FF) band will prevent the BC-230-PB from reading the fieldbus data and thus reduce functionality.
BC-230-PBPROFIBUS PA Diagnostic Monitor, bus powered, Ex approvals, PC software on CD-ROM, manual, certificates, connection cables, and carrying case
Note: User manual, PC software and certificates in English

Fieldbus Shield Digital Leakage Current Clamp - Locating EMC Problems

Measures leakage currents, e.g. leakage and fault currents, and current pick-up of instruments without breaking the circuit. Measurements according to DIN VDE 0701/0702 and the German BetrSichV (BGV A3, VBG 4).
  • Reliably Detects Even Very Small Improper Shield Currents Resulting from EMC Problems.
Fieldbus Shield Digital Leakage Current Clamp

Functionality

Included in Package

  • Leakage current measurement
  • Differential current measurement
  • Voltage and resistance measurement
  • Frequency range for AC current / voltage 40 Hz...1 kHz
  • Acoustical continuity test
  • MIN/MAX and relative value measurement
  • Manual selection of the measurement range
  • Integrated data hold
  • Additional analog bar graph display
  • Clamp opening 30 mm
  • Auto power off

Digital leakage current clamp, 2 batteries 1.5 V IEC LR6, carrying case, measuring cables (1 x red, 1 x black) and user manual.

Order Number:

PB-LSZ-CHB3


Interface for Providing an Access Point to Test PROFIBUS Networks if the D-sub Connectors have no Service Socket or if the Devices are Connected via Terminal Block

Provides an access point for testing PROFIBUS networks if the D-sub connectors have no service socket or if the stations are connected via terminal block.
  • Allows Testing the Bus During Operation
  • Exchange of Bus Devices at the Beginning or End of the Bus Without Causing Problems on the Bus
D-Sub Service Interface

Application

The service interface is top hat rail mounted. An external 24 VDC power source is required for power supply to the terminating resistor in the PROFIBUS connector included in the package. The service interface can thus be used as an active bus termination at the beginning or end of the bus. If the PLC allows dropping and adding bus stations on the live bus, the service interface offers the possibility to exchange the first and last bus stations without causing problems on the bus. Application example:

Application Example D-Sub Service Interface

Included in Package

PBMB adapter and 90° angled PROFIBUS connector with switchable terminating resistor, strain relief and screw terminal technology.

Order Number:

BC-PBMB-PB-S


Interface for Providing an Access Point to Test PROFIBUS Networks With M12 Connectors

Provides an access point for testing PROFIBUS networks with M12 connectors.
  • Allows Testing the Bus During Operation
M12 Service Interface

Application

The service interface is inserted between two bus stations. When not in use, the service output of the T piece is closed with an end cap. At baud rates of 1.5 Mbit/s or higher, use the supplied cable to ensure that the required minimum distance between bus stations is maintained. Application example:

Application Example M12 Service Interface

Downloads

Included in Package

T piece (protection class IP68) with end cap and a 1 m DP cable fitted with a male/female M12 connector on each end.

Order Number:

BC-M12DP-PB